Features :
With this relay you are ideally equipped for the future: it offers security of investment and also saves on operating costs.
- High-speed tripping time
- Impedance setting range allows very small settings for the protection of very short lines
- Self-setting detection for power swing frequencies up to 7 Hz
- Current transformer saturation detector prevents non-selective tripping by distance protection in the event of CT saturation.
- Phase-segregated teleprotection for improved selectivity and availability
- Digital relay-to-relay communication by means of an integrated serial protection data interface
- Adaptive auto-reclosure (ADT)
Hardware
- Binary inputs: 5 to 33
- Binary outputs: 6 to 33
- Power relays: 4 / 8
- Text display
- Surface-mounting or flush-mounting housing
Communication interfaces
- System port
– IEC 61850– IEC 60870-5-103
– PROFIBUS DP
– DNP 3
– 2 analog outputs 0…20 mA
- Service port
– DIGSI 4
– Modem
- 1 serial protection data interface for teleprotection
- Front port
– DIGSI 4
- Time synchronization via IRIG B, DCF 77 or system interface